Title :
Electrical design parameters of all-dielectric-self-supporting fiber optic cable
Author :
Tuominen, Monty W. ; Olsen, Robert G.
Author_Institution :
USDOE, Portland, OR, USA
fDate :
7/1/2000 12:00:00 AM
Abstract :
A lumped circuit model for calculating voltages and currents on all-dielectric self-supporting (ADSS) fiber optic cable near high voltage transmission lines has been developed. The model has been used to show that contamination levels, tower attachment points, relative ADSS and conductor sag and electrical phasing of the conductors are important parameters and must be considered in calculations, especially when determining the possibility of dry band arcs which could lead to cable damage
Keywords :
arcs (electric); optical cables; overhead line mechanical characteristics; poles and towers; power overhead lines; telecommunication transmission lines; all-dielectric-self-supporting fiber optic cable; cable damage; conductor sag; contamination levels; current calculation; dry band arcs; electrical design parameters; electrical phasing; high voltage transmission lines; lumped circuit model; tower attachment points; voltage calculation; Arc discharges; Conductors; Contamination; Corona; Optical design; Optical fiber cables; Optical fibers; Poles and towers; Power cables; Voltage;
Journal_Title :
Power Delivery, IEEE Transactions on