DocumentCode
1387722
Title
An efficient approach for reducing harmonic voltage distortion in distribution systems with active power line conditioners
Author
Chang, Tien-Ting ; Chang, Hong-Chan
Author_Institution
Dept. of Electr. Eng., Nat. Taiwan Inst. of Technol., Taipei, Taiwan
Volume
15
Issue
3
fYear
2000
fDate
7/1/2000 12:00:00 AM
Firstpage
990
Lastpage
995
Abstract
This paper presents a combined differential evolution/multiple gradient summation approach for reducing harmonic distortion with active power line conditioners (APLCs). The purpose of this approach is to minimize the total injection currents of APLC´s while satisfying harmonic standards and practical constraints such as the individual harmonic voltage distortion, total harmonic voltage distortion limits, and the commercially available discrete sizes of the APLCS. The proposed approach was tested on an 18-bus radial distribution system. Results obtained show that the proposed approach can effectively solve the APLC installation problem
Keywords
distribution networks; harmonic distortion; power harmonic filters; power system harmonics; active power line conditioners; distribution systems; harmonic standards; harmonic voltage distortion reduction; total injection currents; Harmonic distortion; Impedance; Passive filters; Power harmonic filters; Power system harmonics; Resistors; Resonance; System testing; Total harmonic distortion; Voltage;