• DocumentCode
    1387739
  • Title

    Numerical electromagnetic field analysis on lightning surge response of tower with shield wire

  • Author

    Baha, Y. ; Ishii, Masaru

  • Author_Institution
    Doshisha Univ., Kyoto, Japan
  • Volume
    15
  • Issue
    3
  • fYear
    2000
  • fDate
    7/1/2000 12:00:00 AM
  • Firstpage
    1010
  • Lastpage
    1015
  • Abstract
    Lightning surge characteristics of a transmission line comprising a tower, a shield wire and phase conductors are studied with the help of NEC-2. A tower struck by a lightning stroke behaves as an antenna until a traveling wave makes several roundtrips in the tower. During this interval, the tower footing impedance appears to be higher than the footing resistance, and the coupling coefficient between a shield wire and a phase conductor is much lower than that in the TEM mode. These affect the estimation of insulator voltages of transmission towers subject to lightning currents having short rise times. On the basis of these findings, the parameters in the multistory tower model, which has been used widely in EMTP multi-conductor analyzes, are newly proposed
  • Keywords
    EMTP; earthing; electromagnetic fields; lightning protection; poles and towers; power overhead lines; power system analysis computing; power system protection; surge protection; EMTP multi-conductors; coupling coefficient; footing resistance; insulator voltages; lightning surge characteristics; lightning surge response; numerical electromagnetic field analysis; overhead power line towers; tower footing impedance; Conductors; Couplings; Electromagnetic analysis; Electromagnetic fields; Impedance; Insulation; Lightning; Poles and towers; Surges; Wire;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.871367