Title :
Current transients in the small salient-pole alternator during sudden short-circuit and synchronisation events
Author :
Best, Robert J. ; Morrow, D. John ; Crossley, Peter A.
Author_Institution :
Sch. of Electron., Electr. Eng. & Comput. Sci., Queen´s Univ. Belfast, Belfast, UK
Abstract :
Small salient-pole machines, in the range 30 kVA to 2 MVA, are often used in distributed generators, which in turn are likely to form the major constituent of power generation in power system islanding schemes or microgrids. In addition to power system faults, such as short-circuits, islanding contains an inherent risk of out-of-synchronism re-closure onto the main power system. To understand more fully the effect of these phenomena on a small salient-pole alternator, the armature and field currents from tests conducted on a 31.5 kVA machine are analysed. This study demonstrates that by resolving the voltage difference between the machine terminals and bus into direct and quadrature axis components, interesting properties of the transient currents are revealed. The presence of saliency and short time-constants cause intriguing differences between machine events such as out-of-phase synchronisations and sudden three-phase short-circuits.
Keywords :
alternators; distributed power generation; power system faults; power system transients; short-circuit currents; armature currents; current transients; distributed generators; field currents; machine terminals; out-of-phase synchronisations; power system faults; power system islanding; small salient-pole alternator; sudden three-phase short-circuits;
Journal_Title :
Electric Power Applications, IET
DOI :
10.1049/iet-epa.2009.0263