Experimental investigation of insulation parameters affecting power transformer condition assessment using frequency domain spectroscopy
Author
Pradhan, M.K. ; Yew, K.J.H.
Author_Institution
Corp. Res., ABB AB, Vasteras, Sweden
Volume
19
Issue
6
fYear
2012
fDate
12/1/2012 12:00:00 AM
Firstpage
1851
Lastpage
1859
Abstract
In recent years, dielectric relaxation methods in time and frequency domains have been evolved as a tool for the assessment of transformer insulation. However, it has been observed that the results of these tests are highly influenced by several factors viz. the temperature of the insulation, the magnitude of the test voltage, the geometry of transformer insulation structure. In the present work, a detailed analysis of the influence of the above-mentioned factors on the dielectric response data is presented by performing measurements on a prorated transformer model. A novel experimental procedure is suggested to acquire a database to study the effect of insulation duct geometry on the relaxation measurements. Possible corrective actions are suggested to improve transformer insulation diagnosis.
Keywords
dielectric relaxation; frequency-domain analysis; geometry; power transformer insulation; spectroscopy; time-domain analysis; dielectric relaxation methods; dielectric response data; frequency domain spectroscopy; insulation duct geometry; power transformer condition assessment; relaxation measurements; time domains; transformer insulation diagnosis; Aging; Moisture; Oil insulation; Power transformer insulation; Temperature measurement; dielectric polarization; frequency domain analysis; insulation diagnosis; insulation geometry; power transformer; prototype;
fLanguage
English
Journal_Title
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher
ieee
ISSN
1070-9878
Type
jour
DOI
10.1109/TDEI.2012.6396940
Filename
6396940
Link To Document