DocumentCode :
1391018
Title :
Experimental investigation of insulation parameters affecting power transformer condition assessment using frequency domain spectroscopy
Author :
Pradhan, M.K. ; Yew, K.J.H.
Author_Institution :
Corp. Res., ABB AB, Vasteras, Sweden
Volume :
19
Issue :
6
fYear :
2012
fDate :
12/1/2012 12:00:00 AM
Firstpage :
1851
Lastpage :
1859
Abstract :
In recent years, dielectric relaxation methods in time and frequency domains have been evolved as a tool for the assessment of transformer insulation. However, it has been observed that the results of these tests are highly influenced by several factors viz. the temperature of the insulation, the magnitude of the test voltage, the geometry of transformer insulation structure. In the present work, a detailed analysis of the influence of the above-mentioned factors on the dielectric response data is presented by performing measurements on a prorated transformer model. A novel experimental procedure is suggested to acquire a database to study the effect of insulation duct geometry on the relaxation measurements. Possible corrective actions are suggested to improve transformer insulation diagnosis.
Keywords :
dielectric relaxation; frequency-domain analysis; geometry; power transformer insulation; spectroscopy; time-domain analysis; dielectric relaxation methods; dielectric response data; frequency domain spectroscopy; insulation duct geometry; power transformer condition assessment; relaxation measurements; time domains; transformer insulation diagnosis; Aging; Moisture; Oil insulation; Power transformer insulation; Temperature measurement; dielectric polarization; frequency domain analysis; insulation diagnosis; insulation geometry; power transformer; prototype;
fLanguage :
English
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher :
ieee
ISSN :
1070-9878
Type :
jour
DOI :
10.1109/TDEI.2012.6396940
Filename :
6396940