DocumentCode
1391034
Title
Effects of paper-aged state on space charge characteristics in oil-impregnated paper insulation
Author
Shi-Qiang Wang ; Guan-Jun Zhang ; Hai-Bao Mu ; Da Wang ; Min Lei ; Suwarno, S. ; Tanaka, Yuichi ; Takada, Tatsuo
Author_Institution
State Key Lab. of Electr. Insulation & Power Equip., Xi´an Jiaotong Univ., Xi´an, China
Volume
19
Issue
6
fYear
2012
fDate
12/1/2012 12:00:00 AM
Firstpage
1871
Lastpage
1878
Abstract
Oil-paper compound insulation has been widely used in power transformers for quite a long time because of its good performance. The paper insulation degrades under the combined stresses of thermal, electrical and chemical stresses during routine operations, resulting in the reduction of its degree of polymerization (DP) and hence its mechanical and electrical strength. Space charges in a dielectric material have a close relation to its electrical performance. Therefore, in this work, the effect of paper-aged states (with different DP values) on the space charge behavior in oil-impregnated paper insulation is investigated, and the pulsed electro-acoustic (PEA) method is used for the space charge distribution measurement. In order to achieve this purpose, new oil-impregnated paper samples are thermally-accelerated aged for different time interval to obtain different DP values, and then the residual oil in each sample is removed, and the Kraft paper samples are dried in a vacuum dry oven. After that, all paper samples are impregnated with new oil, and PEA measurements are performed at room temperature. The experimental results show that, when the external dc voltage is applied on the oil-paper sample, homo-charge injection occurs for all samples. The samples with different aging states exhibit quite different space charge characteristics for both voltage-on and voltage-off conditions. When the aged states are worse, for voltage-on condition, more charges are induced at cathode and anode, as well as more space charges are accumulated in the bulk. For voltage-off condition, the space charge decay rate shows no obvious change for different aged samples.
Keywords
paper; power transformer insulation; pulsed electroacoustic methods; space charge; transformer oil; DP values; Kraft paper; PEA method; anode; cathode; chemical stresses; degree of polymerization reduction; dielectric material; electrical strength; electrical stresses; external dc voltage; homocharge injection; mechanical strength; oil-impregnated paper insulation; oil-paper compound insulation; paper-aged state characteristics; power transformers; pulsed electroacoustic method; routine operations; space charge decay rate; space charge distribution measurement; temperature 293 K to 298 K; thermal stresses; time interval; vacuum dry oven; voltage-off conditions; voltage-on conditions; Aging; Anodes; Cathodes; Charge measurement; Insulation; Space charge; Voltage measurement; aged states; oil-paper insulation; pulsed electro-acoustic (PEA); space charge;
fLanguage
English
Journal_Title
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher
ieee
ISSN
1070-9878
Type
jour
DOI
10.1109/TDEI.2012.6396942
Filename
6396942
Link To Document