DocumentCode
1391089
Title
Location of PD sources in power transformers by UHF and acoustic measurements
Author
Coenen, S. ; Tenbohlen, Stefan
Author_Institution
TLM - Transformer Lifecycle Manage., Siemens AG, Nürnberg, Germany
Volume
19
Issue
6
fYear
2012
fDate
12/1/2012 12:00:00 AM
Firstpage
1934
Lastpage
1940
Abstract
The paper presents the experience of unconventional methods for partial discharge (PD) measurement to detect and localise PD sources in power transformers. The UHF PD measurement method is usable as stand-alone measurement and as a supporting measurement for off- and on-line PD detection. The sensitivity of UHF PD measurements is sufficient and is normally not affected by external disturbances. Especially in noisy surrounding it might be a very helpful method to support other PD measurement techniques for example dissolved gas analysis and acoustic location of PD. Propagation time of UHF signals can be used for geometrical PD location. The accuracy seems to be adequate to determine the phase limb where the PD is located. Additionally, different measurable UHF amplitudes support an estimation of the PD location. However, since transformers rarely possess more than three oil valves for installation of UHF probes, an additional acoustic measurement is usually required for location. Using the knowledge gained from the UHF location, acoustic sensors can be placed near to the PD source at the transformer tank. The paper explains first the fundamentals of PD measurements and PD source location and presents two case studies.
Keywords
acoustic measurement; partial discharge measurement; power transformers; PD source location; UHF amplitudes; UHF measurement method; UHF probes; UHF signals; acoustic measurements; acoustic sensors; dissolved gas analysis; geometrical location; offline PD detection; online PD detection; partial discharge measurement; power transformers; transformer tank; Acoustic measurements; Frequency measurement; Oil insulation; Partial discharges; Power transformers; Probes; UHF measurements; On-site PD measurement; Power transformer; UHF method; acoustic PD location; partial discharges;
fLanguage
English
Journal_Title
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher
ieee
ISSN
1070-9878
Type
jour
DOI
10.1109/TDEI.2012.6396950
Filename
6396950
Link To Document