• DocumentCode
    1391223
  • Title

    Analysis of very fast transient overvoltages (VFTO) from onsite measurements on 800 kV GIS

  • Author

    Yunge Li ; Yong Shang ; Lin Zhang ; Rong Shi ; Wei Shi

  • Author_Institution
    Shaanxi Electr. Power Res. Inst., Xi´an, China
  • Volume
    19
  • Issue
    6
  • fYear
    2012
  • fDate
    12/1/2012 12:00:00 AM
  • Firstpage
    2102
  • Lastpage
    2110
  • Abstract
    In IEC 60071-1 and 62271-102, there is neither standard voltage shape nor standard peak value for very fast transient overvoltages (VFTO). Previous work by other researchers had classified VFTO into two types. A new type was identified in this paper based on an onsite test on a commercially-operated 800 kV GIS. Disconnectors were opened/closed under real operation conditions. Characteristics of the new VFTO type were analyzed, including times of the arc restrikes between the contacts of the disconnectors, trapped charge, damping time constant, magnitude, rise rate, and oscillating frequency. The results of this paper are expected to be of help for the completion of standards on VFTO.
  • Keywords
    IEC standards; arcs (electric); gas insulated substations; gas insulated switchgear; overvoltage; transients; voltage measurement; voltage 800 kV; Gas insulation; Power transformer insulation; Standards; Surges; Transient analysis; Transmission line measurements; Voltage measurement; Digital measurements; EHV substations; disconnector switching; gas insulated switchgear; switching transients; very fast transient overvoltages;
  • fLanguage
    English
  • Journal_Title
    Dielectrics and Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1070-9878
  • Type

    jour

  • DOI
    10.1109/TDEI.2012.6396970
  • Filename
    6396970