• DocumentCode
    1391260
  • Title

    Effect of electrical and thermal stressing on charge traps in XLPE cable insulation

  • Author

    Tzimas, A. ; Rowland, S. ; Dissado, Leonard

  • Author_Institution
    Sch. of Electr. & Electron. Eng., Univ. of Manchester, Manchester, UK
  • Volume
    19
  • Issue
    6
  • fYear
    2012
  • fDate
    12/1/2012 12:00:00 AM
  • Firstpage
    2145
  • Lastpage
    2154
  • Abstract
    Insulation peelings were taken from a single 90 kV ac transmission cable whose segments had been stressed for between ~8000 and 10 000 h either at elevated temperature (363 K) or field 19.5 kV/mm (rms) (T= 293 K). Control peelings were taken from a cable segment that had experienced no stressing. The various peelings were subjected to an endurance test at 70 kV/mm (rms) and T = 363 K, which demonstrated that only those peelings that had experienced thermal stressing had a reduced lifetime compared to the set of control peelings. Space charge measurements made prior to the endurance test showed only negative space charge in all types of peelings and an analysis of the decay dynamics in the control set showed that it resided in two trap distributions at 0.8 to 0.9 eV and 1 to ~1.5 eV. Peelings from a second endurance test (55 kV/mm (rms), T = 363 K) were suspended when the test was terminated at 6088 h. Space charge measurements showed that these samples exhibited positive as well as negative space charge with the positive charge being ~60% of the total. The space charge decay dynamics also showed two trap distributions, ~0.65eV to 0.85 eV and 1eV to ~1.3 eV, with both positive and negative charge in each energy range. Detailed differences in the trap energy range and density in both distributions were found between peelings with different cable histories, and those differences that correlate with a reduction of endurance life are identified. A tentative explanation in terms of anti-oxidant consumption and trap generation by chemical reaction is proffered.
  • Keywords
    XLPE insulation; ageing; insulation testing; power cable insulation; space charge; thermal stresses; XLPE cable insulation; ac transmission cable; antioxidant consumption; charge traps; control peelings; electrical stressing; electron volt energy 0.8 eV to 0.9 eV; electron volt energy 1 eV to 1.5 eV; endurance test; insulation peelings; space charge decay dynamics; space charge measurements; temperature 293 K; temperature 363 K; thermal stressing; time 6088 h; time 8000 h to 10000 h; trap energy range; trap generation; voltage 90 kV; Cable insulation; Electrodes; Materials; Power cables; Space charge; Stress; Thermal stresses; XLPE; ageing; cable insulation; charge traps; electrical ageing; endurance test; negative traps; positive traps; space charge decay;
  • fLanguage
    English
  • Journal_Title
    Dielectrics and Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1070-9878
  • Type

    jour

  • DOI
    10.1109/TDEI.2012.6396975
  • Filename
    6396975