Title :
Implementation and Performance Evaluation of a Reclosing Method for Shunt Reactor-Compensated Transmission Lines
Author :
Mestas, Patricia ; Tavares, Maria Cristina ; Gole, Aniruddha M.
Author_Institution :
Sch. of Electr. & Com puter Eng., Univ. of Campinas (UNICAMP), Campinas, Brazil
fDate :
4/1/2011 12:00:00 AM
Abstract :
This paper proposes a new control method to reduce overvoltages due to three-phase reclosing for shunt compensated transmission lines (TL). The method detects the first minimum voltage region of the beating across the circuit breakers after protection dead time and works independently of voltage zero crossing, reducing significantly the reclosure time. The controller was tested on a Real Time Digital Simulator (RTDS) and its performance was compared to the traditional preinsertion resistor approach and another existing control method.
Keywords :
circuit breakers; overvoltage; performance evaluation; power transmission control; power transmission lines; reactors (electric); circuit breakers; performance evaluation; preinsertion resistor; real time digital simulator; shunt reactor-compensated transmission lines; three-phase reclosing method; voltage zero crossing; Controlled switching; electromagnetic transients; switching overvoltages; three-phase reclosing; transmission lines;
Journal_Title :
Power Delivery, IEEE Transactions on
DOI :
10.1109/TPWRD.2010.2084111