Title :
Optimal compensating scheme for limiting secondary arc current of 1000-kV UHV short parallel lines
Author :
Xu, Z.Y. ; Zhang, Xiaobing ; Yan, X.Q. ; wen, aijun
Author_Institution :
Sch. of Electr. & Electron. Eng., North China Electr. Power Univ., Beijing, China
fDate :
12/1/2012 12:00:00 AM
Abstract :
The optimal single line compensating model is presented and analysed for short 1000-kV UHV parallel lines, to limit secondary arc current and recovery voltage. According to this study, for perfectly transposed 1000-kV lines shorter than 183 km, 750-kV parallel lines shorter than 280 km and 500-kV parallel lines shorter than 500 km, the secondary arc current can be compensated in single line model, and hence achieving the successful selective pole reclosing. Simulations on real time digital simulator (RTDS) have been carried out to evaluate the compensation scheme proposed in this study.
Keywords :
arcs (electric); compensation; power cables; RTDS; UHV short parallel lines; limiting secondary arc current; optimal compensating scheme; optimal single line compensating model; real-time digital simulator; selective pole reclosing; voltage 1000 kV; voltage 500 kV; voltage 750 kV;
Journal_Title :
Generation, Transmission & Distribution, IET
DOI :
10.1049/iet-gtd.2011.0692