• DocumentCode
    1394094
  • Title

    Loading constraints for first swing stability margin enhancement of distributed generation

  • Author

    Bidram, Ali ; Hamedani-golshan, M.-E. ; Davoudi, Ali

  • Author_Institution
    Dept. of Electr. & Comput. Eng., Isfahan Univ. of Technol., Isfahan, Iran
  • Volume
    6
  • Issue
    12
  • fYear
    2012
  • fDate
    12/1/2012 12:00:00 AM
  • Firstpage
    1292
  • Lastpage
    1300
  • Abstract
    This study extracts effective loading constraints for synchronous machine-based distributed generators (SMDGs) in a micro-grid to ensure their post-fault first swing stability. The notion of trajectory sensitivity is used to determine the sensitivity of the SMDGs rotor angles and velocities with respect to the mechanical input power. Then, appropriate loading constraints for SMDGs are calculated for a set of pre-specified faults. The proposed methodology can be used for a micro-grid with an arbitrary number of SMDGs, under various fault scenarios, as well as both grid-connected and autonomous (islanded) modes of operation. The proposed methodology is verified using time-domain simulation of a modified benchmark system of the IEEE standard 399-1997.
  • Keywords
    IEEE standards; distributed power generation; power grids; power system stability; rotors; sensitivity; synchronous generators; time-domain analysis; IEEE standard 399-1997; SMDG; SMDG rotor angles; autonomous modes; distributed generation; first swing stability margin enhancement; grid-connected modes; islanded modes; loading constraints; microgrid; post-fault first swing stability; synchronous machine-based distributed generators; trajectory sensitivity;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission & Distribution, IET
  • Publisher
    iet
  • ISSN
    1751-8687
  • Type

    jour

  • DOI
    10.1049/iet-gtd.2012.0018
  • Filename
    6403946