DocumentCode :
1395733
Title :
Partial discharge-induced degradation characteristics of insulating materials of gas-filled power transformers
Author :
Okabe, Shigemitsu ; Ueta, Genyo ; Wada, Haruhisa ; Okubo, Hitoshi
Author_Institution :
Tokyo Electr. Power Co., Yokohama, Japan
Volume :
17
Issue :
6
fYear :
2010
Firstpage :
1715
Lastpage :
1723
Abstract :
The soundness of a transformer under an operating voltage is evaluated in partial discharge (PD) test of long-duration ac withstand voltage test. At present, the same criteria for evaluating oil-filled transformers are adopted as those for evaluating gas-filled transformers in this PD test. However, gas-filled transformers are made of different insulating materials than those for oil-filled transformers, and therefore they may have different strengths against PDs from oil-filled transformers. Therefore, it is necessary to establish PD evaluation criteria for gas-filled transformers. This paper, as the first step toward this objective, discusses the study of solid insulating materials used in gas-filled transformers in terms of the generated PD magnitudes and the degrees of damage of insulation and examines the harmful PD levels that lower the residual impulse withstand voltage. As a result, it identified the PD-induced degradation patterns of some insulating materials used in gas-filled transformers, i.e., polyethylene terephthalate (PET) films and Nomex® boards and evaluated the harmful PD levels based on the residual impulse withstand voltages. It was also verified that the insulations of pressboards are not degraded even by relatively large PDs.
Keywords :
insulating materials; partial discharges; power transformers; AC withstand voltage test; Nomex boards; PD evaluation criteria; PD test; PD-induced degradation patterns; PET films; gas-filled power transformers; oil-filled transformers; partial discharge-induced degradation characteristics; polyethylene terephthalate films; pressboard insulations; residual impulse withstand voltage; solid insulating materials; Electrodes; Materials; Oil insulation; Partial discharges; Positron emission tomography; Power transformer insulation; Gas-filled power transformer, partial discharge (PD), polyethylene terephthalate (PET) film, Nomex® board, pressboard, residual impulse withstand voltage, harmful partial discharge level, and insulation degradation;
fLanguage :
English
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher :
ieee
ISSN :
1070-9878
Type :
jour
DOI :
10.1109/TDEI.2010.5658221
Filename :
5658221
Link To Document :
بازگشت