• DocumentCode
    1395864
  • Title

    Aging effect on insulation reliability evaluation with weibull distribution for oil-immersed transformers

  • Author

    Tsuboi, Toshihiro ; Takami, Jun ; Okabe, Shigemitsu ; Inami, Kiyoshi ; Aono, Kazuaki

  • Author_Institution
    High Voltage & Insulation Group, Tokyo Electr. Power Co., Yokohama, Japan
  • Volume
    17
  • Issue
    6
  • fYear
    2010
  • Firstpage
    1869
  • Lastpage
    1876
  • Abstract
    In the condition settings of a power-frequency withstand voltage test for substation equipment, an approach based on insulation reliability evaluation using Weibull distribution is available. However, the subjects which should be investigated remains in this method. One of the subjects is that evaluating the insulated reliability for temporary overvoltage caused in an aged equipment by the pre-aging Weibull parameter. In the first place, for an oil-immersed transformer, the breakdown voltage-time (V-t) characteristics of the oil gap were obtained as basic characteristics in the previous experiment. In this experiment the presence or absence of the oil flow was used as a parameter affecting the history of the applied voltage. Also, the validity of the present evaluation approach to temporary overvoltage during operation was examined. In this paper, an insulation characteristic was obtained in consideration of the age-related deterioration in the field. The results were then analyzed in comparison with the insulation characteristics of a new insulating oil. As a result, there was little change affecting the result of insulation reliability evaluation in the Weibull parameters. Consequently, it is reasonable to evaluate the insulation reliability by the V-t characteristic of the new insulating oil.
  • Keywords
    Weibull distribution; ageing; electric breakdown; insulation testing; reliability; transformer oil; Weibull distribution; aging effect; breakdown voltage-time characteristics; insulation reliability evaluation; oil flow; oil gap; oil-immersed transformers; power-frequency withstand voltage test; temporary overvoltage; Aging; Heating; Insulation; Petroleum; Reliability; Voltage measurement; Weibull distribution; Power-frequency withstand voltage test, reliability evaluation, Weibull distributions, breakdown (partial discharge inception) voltage-time characteristics, degradation;
  • fLanguage
    English
  • Journal_Title
    Dielectrics and Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1070-9878
  • Type

    jour

  • DOI
    10.1109/TDEI.2010.5658240
  • Filename