• DocumentCode
    1396652
  • Title

    Investigations on the failure modes of XLPE cables and joints

  • Author

    Nugamani, H.N. ; Channakeshava

  • Author_Institution
    Central Power Res. Inst., Bangalore, India
  • Volume
    13
  • Issue
    3
  • fYear
    1998
  • fDate
    7/1/1998 12:00:00 AM
  • Firstpage
    706
  • Lastpage
    711
  • Abstract
    The work reported in this paper pertains to the investigations on the cross-linked polyethylene (XPLE) cable systems in the presence of water and other electrolytes in contact with the conductor. In this connection, several diagnostic test procedures have been instituted which reveal the status of the dielectric at any point of time. While evaluating different types of joints, it has been observed that two modes of failure are operative, while one is due to electrical effect, the other is essentially due to mechanical effect
  • Keywords
    XLPE insulation; cable jointing; failure analysis; insulation testing; power cable insulation; power cable testing; XLPE cable joints; XLPE cables; conductor; cross-linked polyethylene; diagnostic test procedures; electrical effect; electrolytes; failure modes; mechanical effect; water; Aluminum; Cable insulation; Chemicals; Conductors; Copper; Dielectrics; Electric breakdown; Stress; Voltage; Water resources;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.686963
  • Filename
    686963