• DocumentCode
    1396663
  • Title

    Study on an after-laying test for a long-distance GIL

  • Author

    Araki, Takeshi ; Nishima, H. ; Hata, Hiroki ; Yamaguchi, Hitoshi ; Yamauchi, Takashi ; Miyashita, Makoto

  • Author_Institution
    Sumitomo Electr. Ind. Ltd., Osaka
  • Volume
    13
  • Issue
    3
  • fYear
    1998
  • fDate
    7/1/1998 12:00:00 AM
  • Firstpage
    718
  • Lastpage
    727
  • Abstract
    Technologies for the after-laying test of long-distance SF6 gas insulated transmission line (GIL) have been developed for the detection of partial discharge (PD) and contact defects. We constructed a long (168 m) test line in a deep tunnel and clarified the propagation characteristics of PD signals through the GIL as well as the spatial sensitivity and S/N characteristics of PD sensors for locating metallic particles. We have also proposed the application of a fiber-optic temperature distribution sensor for locating contact defects and confirmed the validity of this sensor for the GIL test line
  • Keywords
    SF6 insulation; cable laying; fibre optic sensors; insulation testing; partial discharges; power cable insulation; power cable testing; power transmission lines; temperature distribution; temperature measurement; 168 m; 275 kV; PD signals propagation; S/N characteristics; SF6; SF6 gas insulated transmission line; after-laying test; contact defects; deep tunnel; fiber-optic temperature distribution sensor; metallic particles location; partial discharge detection; propagation characteristics; spatial sensitivity; Conductors; Gas insulated transmission lines; Insulation; Optical fiber devices; Optical fiber sensors; Optical fiber testing; Partial discharges; Sensor phenomena and characterization; Temperature distribution; Temperature sensors;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.686965
  • Filename
    686965