Title :
Investigation and mitigation of harmonic amplification problems caused by single-tuned filters
Author :
Wu, Chi-Jui ; Chiang, Jung-Chen ; Yen, Shih-Shong ; Liao, Ching-Jung ; Yang, Jin-Shyr ; Guo, Tzong-Yih
Author_Institution :
Dept. of Electr. Eng., Nat. Taiwan Inst. of Technol., Taipei, Taiwan
fDate :
7/1/1998 12:00:00 AM
Abstract :
This paper investigates the harmonic amplification problems in a plastics plant and the appropriate mitigation methods. Four single-tuned filters (LC filters) were installed to eliminate the harmonic currents from three 6-pulse rectifiers. However, after the capacitance reduction of some filter capacitors, the driving point impedance at the frequency of 8th order harmonic increased severely and the harmonic current of this order was amplified. There were many failures of the power filter capacitors. Field measurements and computer simulations are used to verify the disturbance problems. Finally, two high-pass damped filters are recommended to replace the original single-tuned filters. The amplification problems at some even-order harmonics can be avoided
Keywords :
AC-DC power convertors; harmonic distortion; industrial power systems; load (electric); plastics industry; power capacitors; power filters; power system analysis computing; power system harmonics; power system measurement; rectifying circuits; 8th order harmonic; capacitance reduction; computer simulation; disturbance problems; driving point impedance; even-order harmonics; field measurements; harmonic amplification problems; harmonic currents elimination; high-pass damped filters; mitigation methods; plastics plant; power filter capacitors; single-tuned power harmonic filters; six-pulse rectifiers; Capacitance; Capacitors; Computer simulation; Distortion measurement; Harmonic distortion; Impedance; Plastics; Power harmonic filters; Power system harmonics; Rectifiers;
Journal_Title :
Power Delivery, IEEE Transactions on