• DocumentCode
    1397961
  • Title

    3-D nonlinear transient electromagnetic analysis of short circuit electromagnetic forces in a three-phase enclosure-type gas insulated bus

  • Author

    Takeuchi, Toshie ; Yoshizawa, Toshiyuki ; Kuse, Yuko ; Hama, Hiroyuki

  • Author_Institution
    Adv. Technol. R&D Center, Mitsubishi Electr. Corp., Hyogo, Japan
  • Volume
    36
  • Issue
    4
  • fYear
    2000
  • fDate
    7/1/2000 12:00:00 AM
  • Firstpage
    1754
  • Lastpage
    1757
  • Abstract
    An accurate analysis of short circuit electromagnetic forces in a three-phase enclosure-type gas insulated bus (GIB) has been performed. The analysis clarified the effects of the eddy currents (skin effect) and the nonlinear permeability on the materials. The calculated magnetic fields agree with the measured fields. The electromagnetic force analysis considering the skin effect and the nonlinear permeability of the magnetic materials is important in view of reducing the GIB size
  • Keywords
    busbars; eddy currents; electromagnetic forces; finite element analysis; gaseous insulation; magnetic permeability; short-circuit currents; skin effect; substations; 3-D nonlinear transient electromagnetic analysis; 3D finite element methods; eddy currents; magnetic fields; nonlinear permeability; short circuit electromagnetic forces; skin effect; substations; three-phase enclosure-type gas insulated bus; Circuits; Electromagnetic analysis; Electromagnetic forces; Electromagnetic transients; Magnetic analysis; Magnetic field measurement; Magnetic materials; Permeability; Skin effect; Transient analysis;
  • fLanguage
    English
  • Journal_Title
    Magnetics, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9464
  • Type

    jour

  • DOI
    10.1109/20.877783
  • Filename
    877783