Proximity effects on the ground fault current distribution within the earthing system formed by a substation and the associated transmission lines
Author :
Nahman, J.M.
Author_Institution :
Fac. of Electr. Eng., Belgrade Univ., Yugoslavia
Volume :
135
Issue :
6
fYear :
1988
fDate :
11/1/1988 12:00:00 AM
Firstpage :
497
Lastpage :
502
Abstract :
The analysis of currents flowing through a substation earth electrode and through earth wires of overhead lines, connected to the substation for ground faults within the substation, is performed, including the proximity effects between the substation and the earth electrodes of the line towers. Comparison of the results obtained using the complete model suggested by the authors, with the results obtained ignoring the proximity effects, for typical cases, has shown that the proximity of the earth electrodes might considerably affect the ground current distribution and therefore it must be taken into account in certain circumstances. Relatively simple expressions are derived for evaluation of currents flowing through different parts of earthing systems that cover the proximity effects
Keywords :
earth electrodes; earthing; fault currents; power overhead lines; substations; earth electrode; earth wires; earthing system; ground current distribution; ground fault current distribution; line towers; overhead lines; proximity effects; substation; transmission lines;