DocumentCode
140526
Title
Combined topological indices for distributed generation planning
Author
Formigli, Carlos ; Rovatti, Riccardo ; Setti, Gianluca
Author_Institution
ARCES, Univ. of Bologna, Bologna, Italy
fYear
2014
fDate
19-22 Feb. 2014
Firstpage
1
Lastpage
5
Abstract
We show how outage shift factors can be used to define a synthetic indicator of node importance in power grids. Such indicator can be combined with other indices to jointly assess the criticality of grid buses as far as robustness with respect to blackouts is concerned. As an example we use it jointly with Electrical Betweenness to select power sources locations in a distributed generation framework. Simulation indicates that blackout rejection is non negligible enhanced by this combined approach.
Keywords
distributed power generation; load flow; power generation planning; power grids; probability; blackout rejection; combined topological indices; distributed generation framework; distributed generation planning; electrical betweenness; grid buses; node importance; outage shift factors; power grids; power sources locations; synthetic indicator; Distributed power generation; Generators; Indexes; Load modeling; Power grids; Security; Vectors;
fLanguage
English
Publisher
ieee
Conference_Titel
Innovative Smart Grid Technologies Conference (ISGT), 2014 IEEE PES
Conference_Location
Washington, DC
Type
conf
DOI
10.1109/ISGT.2014.6816481
Filename
6816481
Link To Document