• DocumentCode
    1405919
  • Title

    Probabilistic Multistage PMU Placement in Electric Power Systems

  • Author

    Aminifar, Farrokh ; Fotuhi-Firuzabad, Mahmud ; Shahidehpour, Mohammad ; Khodaei, Amin

  • Author_Institution
    Electr. Eng. Dept., Sharif Univ. of Technol., Tehran, Iran
  • Volume
    26
  • Issue
    2
  • fYear
    2011
  • fDate
    4/1/2011 12:00:00 AM
  • Firstpage
    841
  • Lastpage
    849
  • Abstract
    This paper presents an optimization model for the calculation of the minimum number of phasor measurement units (PMUs) in electrical power networks. The problem constraint is a predefined probability of observability associated with each bus. The mixed-integer programming is used for the proposed optimization and an efficient linearization technique is proposed to convert the nonlinear function representing the probability of observability into a set of linear expressions. The PMU placement is staged in a multi-year planning horizon due to financial and physical constraints. The average probability of observability is maximized at the intermediate planning stages, subject to a limited number of PMU placements, that would satisfy the horizon year schedule. In addition, network expansion scenarios associated with intermediate stages are taken into account. Numerical studies are conducted on a nine-bus system and the IEEE 57-bus system and the results are analyzed.
  • Keywords
    electric power generation; integer programming; linearisation techniques; power system measurement; electric power systems; linearization technique; mixed-integer programming; optimization model; phasor measurement units; probabilistic multistage PMU placement; Mixed-integer programming (MIP); optimal placement of phasor measurement units; probabilistic observability;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2010.2090907
  • Filename
    5669370