Title :
Reestablishing excitation of a loaded alternator
Author :
Higgins, D. D. ; Wild, E.
Author_Institution :
Commonwealth Edison Co., Chicago, Ill.
Abstract :
Operating tests on large turbine-generators indicate that following the accidental opening of the field switch of a loaded machine, service should be restored by closing this switch as soon as possible, without removing the generator from the bus.
Keywords :
Alternators; Companies; Demagnetization; Generators; Switches; Turbines; Windings;
Journal_Title :
Electrical Engineering
DOI :
10.1109/EE.1932.6429678