DocumentCode :
1407051
Title :
Reestablishing excitation of a loaded alternator
Author :
Higgins, D. D. ; Wild, E.
Author_Institution :
Commonwealth Edison Co., Chicago, Ill.
Volume :
51
Issue :
2
fYear :
1932
Firstpage :
119
Lastpage :
120
Abstract :
Operating tests on large turbine-generators indicate that following the accidental opening of the field switch of a loaded machine, service should be restored by closing this switch as soon as possible, without removing the generator from the bus.
Keywords :
Alternators; Companies; Demagnetization; Generators; Switches; Turbines; Windings;