DocumentCode
1407768
Title
Impulse tests on a substation
Author
Collins, H. W. ; Piepho, E. E. ; Torok, J. J.
Author_Institution
Detroit Edison Co., Detroit, Michigan
Volume
51
Issue
5
fYear
1932
fDate
5/1/1932 12:00:00 AM
Firstpage
304
Lastpage
306
Abstract
Severe flashovers have occurred in ungrounded 4,800-volt distribution substations in Detroit. Impulse tests have proved that these were caused by surges reflected from regulator windings, but can be prevented by the proper placing of lightning arresters.
Keywords
Arresters; Lightning; Regulators; Substations; Surges; Voltage control; Wires;