• DocumentCode
    1407815
  • Title

    Investigation of Factors Affecting the Sustainability of Arcs Below 250 V

  • Author

    Lang, Michael J. ; Jones, Kenneth

  • Author_Institution
    Mersen, Newburyport, MA, USA
  • Volume
    48
  • Issue
    2
  • fYear
    2012
  • Firstpage
    784
  • Lastpage
    793
  • Abstract
    Recent testing with various electrode configurations and insulating barriers suggests that 250-V equipment omitted from arc flash hazard analyses has the potential for burn injury. Research into the sustainability of arcs at these voltages shows that assumptions about the magnitude of these hazards need to be revised. This research enhanced the work of previous efforts by focusing on the sustainability of arcs with fault currents lower than 10 kA. Gap lengths between electrodes, electrode shape, electrode material, and voltage variations are studied for their effects on arc sustainability. A modified barrier design representative of the space around panelboard bus bars is also studied.
  • Keywords
    arcs (electric); electrochemical electrodes; fault currents; insulation; power apparatus; arc flash hazard analyses; arcs sustainability; electrode configurations; electrode material; electrode shape; fault currents; insulating barriers; power equipment; voltage 250 V; voltage variations; Arc discharges; Bars; Conductors; Electrodes; Fault currents; Hazards; Testing; Arc fault sustainability; arc flash hazard testing; effect of insulating barriers; plasma; terminated vertical conductors; terminated vertical electrodes; vertical conductors; vertical electrodes;
  • fLanguage
    English
  • Journal_Title
    Industry Applications, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-9994
  • Type

    jour

  • DOI
    10.1109/TIA.2011.2181292
  • Filename
    6112214