• DocumentCode
    1410399
  • Title

    Pilot-wire differential-protection characteristics for multiended circuits

  • Author

    Rushton, John

  • Volume
    112
  • Issue
    11
  • fYear
    1965
  • fDate
    11/1/1965 12:00:00 AM
  • Firstpage
    2095
  • Lastpage
    2102
  • Abstract
    The steady-state characteristics of differential-protection systems for multiended circuits are discussed and alternative characteristics, which appear to give improved performance, are proposed. Circuits for the implementation of these characteristics, incorporating pilot-circuit compensation and amplitude comparators, are presented. A design basis for compensation circuits is given by expressing the comparator performance in terms of its admittance-measurement characteristics and associating these with the input-admittance characteristics of the pilot circuit. By this means it is possible to investigate the various comparator arrangements, and to determine the most suitable arrangement for the protection of a multiended circuit. By a transformation of axis, the admittance-plane characteristics can be presented in terms of the ratio of the comparison quantity at one end to the summated quantity at the remaining ends, making it possible to investigate power-system fault conditions on the same diagram to determine available discriminating margins.
  • Keywords
    power transmission lines; relay protection; telecommunication cables;
  • fLanguage
    English
  • Journal_Title
    Electrical Engineers, Proceedings of the Institution of
  • Publisher
    iet
  • ISSN
    0020-3270
  • Type

    jour

  • DOI
    10.1049/piee.1965.0348
  • Filename
    5247468