DocumentCode :
1410660
Title :
Development of Ultra-Low-Noise Transformer Technology
Author :
Girgis, Ramsis S. ; Bernesjö, Mats S. ; Thomas, Scott ; Anger, Jan ; Chu, Donald ; Moore, Harold R.
Author_Institution :
ABB Power Transformer Plant, St. Louis, MO, USA
Volume :
26
Issue :
1
fYear :
2011
Firstpage :
228
Lastpage :
234
Abstract :
Strict limits of the revised noise ordinance of New York City require power transformers to have ultra-low levels at each of the frequencies of transformer noise at full load and overexcitation. This paper describes the development of the technology that allowed successful design and production of ultra-low-noise power transformers recently delivered to Consolidated Edison of New York City. The paper presents results achieved by this development effort in the areas of accurate calculation of core resonance frequencies, frequency spectrum of core noise, and load noise. It also presents other aspects of the technology development, such as de-coupling of active parts vibrations from the tank, proper design of tank-plate fields and tank bracing, proper transformer mounting techniques, and accurate measurement of low noise levels in the factory. Finally, this paper presents the difference in design of the generations of these transformers produced at different stages of this development effort.
Keywords :
power system planning; power transformers; Consolidated Edison; New York City; core noise; core resonance frequencies; frequency spectrum; load noise; noise ordinance; tank bracing; tank-plate fields; ultra-low-noise power transformers; ultra-low-noise transformer technology; Frequency measurement; Noise; Noise level; Noise measurement; Power transformers; Resonant frequency; Transformer cores; Core noise; core resonance; load noise; low-noise transformers; sound level measurements;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2010.2070812
Filename :
5673870
Link To Document :
بازگشت