DocumentCode
1410812
Title
Analogue investigation of water cooling of e.h.v. cables
Author
Lis, J. ; Thelwell, M.J.
Volume
112
Issue
2
fYear
1965
fDate
2/1/1965 12:00:00 AM
Firstpage
335
Lastpage
341
Abstract
The paper describes the use of an electrical-resistance analogue to investigate the factors governing the current rating of water-cooled underground transmission cables. The effects of cooling-water temperature, soil thermal resistivity, cable size and spacing, joints and possible alternative dielectric materials on circuit rating are examined and discussed. The results indicate that water cooling can increase the rating of a cable by between 50% and 150%, depending on the method of cooling adopted. The circuit rating will, however, depend on the efficiency of cooling at the joints.
Keywords
cooling; network analysers; power cables; underground cables;
fLanguage
English
Journal_Title
Electrical Engineers, Proceedings of the Institution of
Publisher
iet
ISSN
0020-3270
Type
jour
DOI
10.1049/piee.1965.0052
Filename
5247535