Abstract
This case study shows the application of the calculation method based on the detailed thermal-hydraulic network model. The method is applied for the thermal design of oil power transformer of rated power 750 MVA in oil-directed, air-forced cooling mode; rated powers are also specified for oil-natural, air-forced and oil-natural, air-natural cooling modes. The results of the calculations using developed software for three cooling modes are compared with the results of the heat-run test of the transformer equipped with fiber-optic sensors. In addition to confirmation of the accuracy of the model, this paper demonstrates the full power of the integrated method (inner heating and outer cooling) for thermal calculations. All relevant components (pressure drops, oil flows, oil temperatures, etc.) in different cooling modes are obtained from the model and exposed in this paper.
Keywords
cooling; fibre optic sensors; power transformer insulation; transformer oil; air forced cooling mode; apparent power 750 MVA; fiber optic sensor; oil directed cooling mode; oil natural cooling mode; oil power transformer; thermal calculation; thermal hydraulic network model; Conductors; Cooling; Oil insulation; Software; Temperature measurement; Windings; Hot-spot temperature; oil-directed, air-forced (ODAF) cooling; oil-natural, air-forced (ONAF) cooling; oil-natural, air-natural (ONAN) cooling; thermal design; transformer;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2011.2176543
Filename
6118314
Link To Document