DocumentCode :
1411736
Title :
Dry-band discharges on polluted silicone rubber insulation: control and characterization
Author :
Waters, R.T. ; Haddad, A. ; Griffiths, H. ; Harid, N. ; Charalampidis, P. ; Sarkar, P.
Author_Institution :
High Voltage Energy Syst. Group, Cardiff Univ., Cardiff, UK
Volume :
18
Issue :
6
fYear :
2011
fDate :
12/1/2011 12:00:00 AM
Firstpage :
1995
Lastpage :
2003
Abstract :
Inclined-plane tests of silicone-rubber samples prepared with textured patterns of hemispherical protuberances are described. These are compared with the results obtained for conventional non-textured plane-surface samples of the same material. A remarkable improvement is achieved by such texturing: a material which normally fails the test is enabled to satisfy the standard test criteria, and the tracking and erosion of the samples caused by the tests are significantly reduced. These texturing techniques are currently being extended to prototype composite insulators. It is shown that this improvement for textured samples is a result of the formation of a stable, controlled dry band on the polluted surface. Although discharge inception occurs across the band, these discharges result in a fall, rather than an increase, of the leakage current. The transition to a higher current arc phase is thus inhibited, compared with non-textured samples for which stable dry bands did not occur. These observations of reproducible dry band breakdown also provide an opportunity to characterize experimentally the electrical properties of these discharges. A recent proposed model represents the dry-band discharge as a streamer-spark structure, in contrast to the standard model of an arc-like interdependence of current and voltage. These two models are tested against the present new data, and the discharge is shown to have streamer characteristics.
Keywords :
arcs (electric); composite insulators; discharges (electric); electric breakdown; insulator contamination; insulator testing; silicone rubber insulators; arc-like interdependence; controlled dry band; discharge inception; dry-band discharge; electrical property; hemispherical protuberance; inclined-plane test; leakage current; nontextured plane-surface sample; polluted silicone rubber insulation; polluted surface; prototype composite insulator; reproducible dry band breakdown; stable dry band; standard test criteria; streamer characteristics; streamer-spark structure; textured pattern; texturing technique; Discharges; Electrodes; Leakage current; Rubber; Surface contamination; Surface discharges; Surface texture; Outdoor insulation; arc; corona; dry-banding; high voltage; insulation contamination; insulator testing; mathematical model; pollution; silicone rubber insulation; spark;
fLanguage :
English
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher :
ieee
ISSN :
1070-9878
Type :
jour
DOI :
10.1109/TDEI.2011.6118637
Filename :
6118637
Link To Document :
بازگشت