Title :
Analysis of a Commercial Wind Farm in Taiwan Part I: Measurement Results and Simulations
Author :
Wang, Li ; Yeh, Tai-Her ; Lee, Wei-Jen ; Chen, Zhe
Author_Institution :
Dept. of Electr. Eng., Nat. Cheng Kung Univ., Tainan, Taiwan
Abstract :
This paper presents both steady-state performance and dynamic simulations of a commercial wind farm (WF) in Taiwan through field measurement results and computer simulations. The companion paper in Part II discusses the dynamic and transient analyzed results of using current-limit reactors (CLRs) and load tap changers on power-quality improvement of the studied WF. With 23 2-MW DFIG-type wind turbine generators, this WF is connected to the 161-kV extra high-voltage substation of Taiwan Power System through a 23/161-kV 60-MVA step-up main transformer from six feeders with CLRs. Through comparing field measured results, this paper establishes a simulation model to simulate and analyze the steady-state and dynamic characteristics of the studied WF which is subject to disturbance conditions under different wind-speed conditions.
Keywords :
asynchronous generators; current limiting reactors; electric field measurement; transient analysis; wind power plants; DFIG type wind turbine generator; Taiwan power system; commercial wind farm; computer simulation; current limiting reactor; dynamic simulations; field measurement result; high-voltage substation; load tap changer; power quality improvement; steady-state performance; step-up main transformer; transient analysis result; voltage 161 kV; Current-limit reactor (CLR); doubly fed induction generator (DFIG); load tap changer (LTC); wind farm (WF); wind turbine generator (WTG);
Journal_Title :
Industry Applications, IEEE Transactions on
DOI :
10.1109/TIA.2010.2101991