• DocumentCode
    1412530
  • Title

    Impacts of Superconducting Cables on the Dynamic Response of Current Transformers and Protective Relaying Devices

  • Author

    Johnson, Brian K. ; Fischer, Normann ; Xia, Yu

  • Author_Institution
    Univ. of Idaho, Moscow, ID, USA
  • Volume
    21
  • Issue
    3
  • fYear
    2011
  • fDate
    6/1/2011 12:00:00 AM
  • Firstpage
    2149
  • Lastpage
    2152
  • Abstract
    Replacing conventional ac transmission lines with superconducting cables provides performance advantages since superconducting cables have lower series inductance and very low ac resistance. However, the very low resistance will also have an impact on the dynamic response of current transformers (CTs) and on the response of protective relays that process their current measurements. Whenever a short circuit occurs on an ac power system the resulting current will have both fundamental frequency ac response and a decaying dc offset. The amplitude of the dc offset is dependent on the point on the ac voltage wave where the fault occurs, which is random. The rate of this decay depends on the R-L time constant of the ac circuit involved in the current path. A larger time constant increases the odds that a CT will enter saturation. Superconducting cables will increase the R-L time constant, and potentially increase the severity of CT saturation, creating error in the secondary current used by the protective relays. For many protection functions this error will delay the protective action, but in a few cases it may cause circuit breakers to trip in error. This paper will model a sample system with differing levels of penetration of superconducting cables and look at the impact of the superconducting cables on the dynamic CT response and on different protective relay functions and discuss potential solutions.
  • Keywords
    circuit breakers; current transformers; dynamic response; frequency response; power system protection; relay protection; superconducting cables; AC circuit; AC power system; AC transmission lines; R-L time constant; circuit breakers; current measurements; current transformers; dynamic CT response; dynamic response; frequency AC response; protective relaying devices; superconducting cables; Circuit faults; Current transformers; Fault currents; Relays; Resistance; Superconducting cables; Current transformers; power transmission protection; superconducting cables; superconducting transmission lines;
  • fLanguage
    English
  • Journal_Title
    Applied Superconductivity, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1051-8223
  • Type

    jour

  • DOI
    10.1109/TASC.2010.2093591
  • Filename