DocumentCode :
1412589
Title :
Assessment of the Impact of SFCL on Voltage Sags in Power Distribution System
Author :
Moon, Jong-Fil ; Lim, Sung-Hun ; Kim, Jae-Chul ; Yun, Sang-Yun
Author_Institution :
Dept. of Electr. Eng., Chungju Nat. Univ., Chungju, South Korea
Volume :
21
Issue :
3
fYear :
2011
fDate :
6/1/2011 12:00:00 AM
Firstpage :
2161
Lastpage :
2164
Abstract :
This paper assesses and analyses the effects of superconducting fault current limiter (SFCL) installed in power distribution system on voltage sags. First of all, resistor-type SFCL is modeled using PSCAD/EMTDC to represent the quench and recovery characteristics based on the experimental results. Next, typical power distribution system of Korea is modeled. When the SFCL is installed in various locations from the starting point to end point of feeders, improvement of voltage sag is evaluated using the Information of Technology Industry Council (ITIC) curve of customer´s loads when a fault occur. Finally, future studies needing to apply SFCL to power distribution system are presented.
Keywords :
distribution networks; power supply quality; power system CAD; superconducting fault current limiters; ITIC curve; Information of Technology Industry Council; Korea; PSCAD/EMTDC; customer loads; power distribution system; quench characteristics; recovery characteristics; resistor-type SFCL; superconducting fault current limiter; voltage sags; Circuit faults; Fault currents; Impedance; Optical character recognition software; Power distribution; Power quality; Voltage fluctuations; ITIC; SFCL; power distribution system; voltage sag;
fLanguage :
English
Journal_Title :
Applied Superconductivity, IEEE Transactions on
Publisher :
ieee
ISSN :
1051-8223
Type :
jour
DOI :
10.1109/TASC.2010.2093592
Filename :
5675721
Link To Document :
بازگشت