DocumentCode :
1414774
Title :
Removing Insertion Impedance Effects From Transformer Admittance Measurements
Author :
Gustavsen, Bjørn
Author_Institution :
SINTEF Energy Res., Trondheim, Norway
Volume :
27
Issue :
2
fYear :
2012
fDate :
4/1/2012 12:00:00 AM
Firstpage :
1027
Lastpage :
1029
Abstract :
Frequency-domain measurements can be used for obtaining a wideband model of a power transformer via its terminal admittance matrix. This paper shows that the current sensor used in the measurements can significantly affect the elements of the obtained admittance matrix by its insertion impedance. The insertion impedance influences diagonal and off-diagonal elements, often leading to asymmetries in the matrix for transformers having a high-voltage ratio. Formulae are developed which are capable of removing these effects. The procedure is demonstrated for a distribution transformer.
Keywords :
electric admittance measurement; power transformers; current sensor; distribution transformer; frequency-domain measurements; high-voltage ratio; insertion impedance effects; off-diagonal elements; terminal admittance matrix; transformer admittance measurements; Admittance; Admittance measurement; Current measurement; Impedance; Impedance measurement; Power transformers; Voltage measurement; Admittance matrix; asymmetry; frequency domain; measurements; transformer; wideband;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2011.2175818
Filename :
6122475
Link To Document :