• DocumentCode
    1415288
  • Title

    Static VAr compensator (STATCOM) based on single-phase chain circuit converters

  • Author

    Ainsworth, J.D. ; Davies, M. ; Fitz, P.J. ; Owen, K.E. ; Trainer, D.R.

  • Author_Institution
    GEC ALSTHOM T&D Power Electron. Syst. Ltd., Stafford, UK
  • Volume
    145
  • Issue
    4
  • fYear
    1998
  • fDate
    7/1/1998 12:00:00 AM
  • Firstpage
    381
  • Lastpage
    386
  • Abstract
    Voltage-sourced converter circuits using gate turn-off (GTO) thyristors have been proposed as an alternative means of providing static VAr compensation (SVC). Such `advanced SVCs´ are classified under the nomenclature STATCOM (STATic COMpensator). The published converter circuits suitable for power system application include the classical Graetz bridge and the multilevel converter. Alternative circuit arrangement has developed with significant advantages in terms of cost and performance; this is in the form of a number of GTO converter links connected in series to form a chain and is referred to as a chain circuit converter. The paper discusses the chain circuit converter and its application to VAr compensation followed by the design and simulated performance of a three-phase STATCOM under both steady state and transient operating conditions. The technical advantages of the chain circuit converter compared with other known arrangements of STATCOM are given. These include good harmonic performance, fast response and improved output at low voltage compared with conventional SVCs. The paper includes comments on the successful testing of two prototype chain links for both leading and lagging reactive currents up to 2000 A peak and concludes with a description of the equipment now being designed for commercial service
  • Keywords
    compensation; harmonic distortion; power system harmonics; reactive power; static VAr compensators; thyristor convertors; 2000 A; GTO voltage-source power converters; STATCOM; classical Graetz bridge; harmonic performance; low voltage output; multilevel power converter; power system application; response; single-phase chain circuit converters; static VAr compensator; steady-state operating conditions; technical advantages; testing; transient operating conditions;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission and Distribution, IEE Proceedings-
  • Publisher
    iet
  • ISSN
    1350-2360
  • Type

    jour

  • DOI
    10.1049/ip-gtd:19982032
  • Filename
    707083