DocumentCode :
1417378
Title :
Static sampling distance relays
Author :
McLaren, P.G.
Author_Institution :
Heriot-Watt University, Department of Electrical & Electronic Engineering, Edinburgh, UK
Volume :
115
Issue :
3
fYear :
1968
fDate :
3/1/1968 12:00:00 AM
Firstpage :
418
Lastpage :
424
Abstract :
A sampling technique has been developed which allows a comparison of instantaneous values derived at different instants of time, thereby dispensing with the need to phase-shift or mix signals derived from the primary line quantities. Both amplitude and phase comparisons are used to derive a variety of impedance characteristics. The relays combine high sensitivity with a high resistance to interference. Detailed results are presented for a current-polarised relay with a characteristic surrounding the probable fault area.
Keywords :
relay protection;
fLanguage :
English
Journal_Title :
Electrical Engineers, Proceedings of the Institution of
Publisher :
iet
ISSN :
0020-3270
Type :
jour
DOI :
10.1049/piee.1968.0076
Filename :
5248586
Link To Document :