DocumentCode :
1418713
Title :
Discharge detection in high-voltage power transformers
Author :
James, R.E.
Author_Institution :
Portsmouth Polytechnic, Department of Electrical & Electronic Engineering, Portsmouth, UK
Volume :
117
Issue :
7
fYear :
1970
fDate :
7/1/1970 12:00:00 AM
Firstpage :
1352
Lastpage :
1362
Abstract :
The paper presents the special problems involved in the detection of discharges within high-voltage power transformers. This is followed by a review of the various location techniques being developed in different parts of the world. Both electrical and ultrasonic methods are considered. It is concluded that a routine test is not yet possible, but suggestions are made regarding the relationship between any such measurement and high-voltage insulation tests. It is emphasised that further information of discharge values obtained under prescribed conditions is essential before acceptance levels can be seriously discussed. Again, a test procedure is suggested. Comment is made on the suitability of existing discharge-detection equipment for measurements on transformers. Evidence indicates that a change might be desirable, possibly in association with a location technique. Finally, it is hoped that the paper will help produce a fuller discussion of the real problems involved in transformer-discharge detection, and perhaps lead to the crystallising of the many and varied ideas which have developed since the previous UK joint publication on the subject.
Keywords :
discharges (electric); transformer testing;
fLanguage :
English
Journal_Title :
Electrical Engineers, Proceedings of the Institution of
Publisher :
iet
ISSN :
0020-3270
Type :
jour
DOI :
10.1049/piee.1970.0259
Filename :
5248813
Link To Document :
بازگشت