• DocumentCode
    1421099
  • Title

    Five years´ experience with ultrahigh-speed reclosing of high-voltage transmission lines

  • Author

    Sporn, Philip ; Muller, C. A.

  • Author_Institution
    American Gas and Electric Service Corporation, New York, N. Y.
  • Volume
    60
  • Issue
    5
  • fYear
    1941
  • fDate
    5/1/1941 12:00:00 AM
  • Firstpage
    241
  • Lastpage
    245
  • Abstract
    The data covering five years´ operating experience with 33 ultrahigh-speed reclosing breaker installations mainly on a large interconnected and integrated high-tension system are presented and analyzed, and conclusions based on this experience are drawn. Out of 71 cases of flashover cited, 65 reclosures were successful and 6 cases of reclosure resulted in restrikes, a record of 91.5 per cent successful reclosures. The conclusions drawn are that not only is actual performance better than appeared possible when the development was first made but that further improvements are possible by further reducing breaker time.
  • Keywords
    Circuit faults; Flashover; Lightning; Poles and towers; Power transmission lines; Relays;
  • fLanguage
    English
  • Journal_Title
    Electrical Engineering
  • Publisher
    ieee
  • ISSN
    0095-9197
  • Type

    jour

  • DOI
    10.1109/EE.1941.6432118
  • Filename
    6432118