DocumentCode :
1421497
Title :
Fault voltage drop and impedance at short-circuit currents in low-voltage circuits
Author :
Schurig, O. R.
Author_Institution :
General Electric Company, Schenectady, N. Y.
Volume :
60
Issue :
6
fYear :
1941
fDate :
6/1/1941 12:00:00 AM
Firstpage :
479
Lastpage :
486
Abstract :
In the paper are presented new data on (1) arc-voltage drop and current-limiting effects for arc faults in bar-conductor structures, (2) current-limiting effect of insulated-cable arc faults, (3) cable impedance in an iron conduit, and (4) impedance of low-voltage switchgear circuit assemblies, derived from tests at short-circuit currents in circuits with open-circuit line-to-line voltages of 208–600 volts at 60 cycles. The currents ranged from less than 10,000 amperes to values as high as 100,000 amperes rms in some cases.
Keywords :
Assembly; Bars; Circuit faults; Conductors; Copper; Impedance; Wires;
fLanguage :
English
Journal_Title :
Electrical Engineering
Publisher :
ieee
ISSN :
0095-9197
Type :
jour
DOI :
10.1109/EE.1941.6432186
Filename :
6432186
Link To Document :
بازگشت