    Circulating-current pilot-wire differential protection system

  • Author

    Gray, C.B.

  • Author_Institution
    University of Bradford, School of Studies in Electrical & Electronic Engineering, Bradford, UK
  • Volume
    114
  • Issue
    6
  • fYear
    1967
  • fDate
    6/1/1967 12:00:00 AM
  • Firstpage
    769
  • Lastpage
    774
  • Abstract
    A circulating-current a.c. pilot-wire differential protection scheme is described in which compensation is provided for the phase shift of the fundamental-frequency signals transmitted over the pilot-wire circuit. Alternative relay characteristics are considered, with particular reference to the desirability of maintaining simultaneous tripping of circuit breakers at both ends of the protected section under all internal-fault conditions. Factors influencing the choice of preferred relay-tripping characteristics are examined, together with a means of modifying a practical pilot circuit to enable the preferred tripping characteristic to be obtained.
  • Keywords
    electrical power systems; protection;