Title :
Performance requirements and test methods for high-voltage a.c.-motor insulation
Author_Institution :
Laurence, Scott and Electromotors Ltd., Norwich, UK
fDate :
10/1/1969 12:00:00 AM
Abstract :
Tha paper deals with the problems of high-voltage (3¿11 kV) insulation for rotating machines of up to 10¿20 MW. A clear distinction is drawn between the problems of design and the testing of the earth and the interturn insulation. Schering-bridge tests for the quality control of earth insulation above 10kV are advocated. A combination of withstand and breakdown tests at the power frequency are related to system surge levels and the impulse performance of rotating machines in recommendations for earth- and interturn-insulation test procedures in the context of existing specifications for allied apparatus. A brief survey of existing information, particularly on impulse problems, is used to support these recommendations.
Keywords :
AC motors; insulation testing; testing;
Journal_Title :
Electrical Engineers, Proceedings of the Institution of
DOI :
10.1049/piee.1969.0317