DocumentCode :
1422275
Title :
Development of insulation structure and enhancement of insulation reliability of 500 kV DC GIS
Author :
Hasegawa, T. ; Yamaji, K. ; Hatano, M. ; Endo, F. ; Rokunohe, T. ; Yamagiwa, T.
Author_Institution :
Kansai Electr. Power Co. Inc., Osaka, Japan
Volume :
12
Issue :
1
fYear :
1997
fDate :
1/1/1997 12:00:00 AM
Firstpage :
194
Lastpage :
202
Abstract :
The paper describes the development of insulation structure and enhancement of insulation reliability of 500 kV DC GIS (gas insulated switchgear). Considering problems of metallic particles and charge accumulation on spacers, the developed insulation structure of GIS consisted of three regions, i.e. the spacer, particle scavenging and nonlevitating regions. Particles could be efficiently scavenged, and the developed GIS withstood all insulation specifications with sufficient margins under the clean and particle-contaminated condition. Now, a long-term site test for one year of the 500 kV DC GIS has been continued since October in 1995
Keywords :
HVDC power transmission; circuit breakers; gas insulated switchgear; insulation testing; reliability; 500 kV; HVDC gas insulated switchgear; charge accumulation; insulation reliability enhancement; insulation structure; metallic particles; nonlevitating regions; particle scavenging; particle-contaminated condition; Conductors; Electrodes; Geographic Information Systems; Insulation; Partial discharges; Samarium; Shape; Surface charging; Testing; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.568241
Filename :
568241
Link To Document :
بازگشت