DocumentCode :
1422358
Title :
Electronic error reduction system for clamp-on probes and measuring current transformers
Author :
Slomovitz, Daniel
Author_Institution :
Fac. de Ingenieria, Univ. de la Republica, Montevideo, Uruguay
Volume :
49
Issue :
6
fYear :
2000
fDate :
12/1/2000 12:00:00 AM
Firstpage :
1278
Lastpage :
1281
Abstract :
An original electronic device for compensating ratio and phase-displacement errors, of measuring current transformers and clamp-on probes, is proposed. It is intended for low-frequency applications (power frequency and its harmonic components), where the magnetizing current is the main cause of measuring errors. This system reduces the magnetic flux in the transformer core, reducing in this way the magnetizing current. The proposed system even reduces the influence of the error produced by the variation of the burden connected to the secondary winding. Large values of burden can be used without effects on the transformer measuring errors. This device can be directly applied to conventional current transformers, connecting the device to the secondary terminals. It is not necessary to use any auxiliary winding or auxiliary core, or any modification of those transformers
Keywords :
current transformers; error compensation; magnetic flux; measurement errors; transformer windings; auxiliary core; auxiliary winding; clamp-on probes; electronic error reduction system; low-frequency applications; magnetic flux; magnetizing current; measuring current transformers; measuring errors; phase-displacement errors; Current measurement; Current transformers; Frequency measurement; Joining processes; Magnetic flux; Phase measurement; Power measurement; Power system harmonics; Probes; Transformer cores;
fLanguage :
English
Journal_Title :
Instrumentation and Measurement, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9456
Type :
jour
DOI :
10.1109/19.893270