• DocumentCode
    1422440
  • Title

    An improved transformer top oil temperature model for use in an on-line monitoring and diagnostic system

  • Author

    Lesieutre, B.C. ; Hagman, W.H. ; Kirtley, J.L., Jr.

  • Author_Institution
    Lab. for Electromagn. & Electron. Syst., MIT, Cambridge, MA, USA
  • Volume
    12
  • Issue
    1
  • fYear
    1997
  • fDate
    1/1/1997 12:00:00 AM
  • Firstpage
    249
  • Lastpage
    256
  • Abstract
    In this paper, the authors examine dynamic models of power transformer top oil temperature for use in an online monitoring and diagnostic system. Data taken from large transformers in the field indicate that the IEEE model of top oil temperature rise over ambient temperature does not adequately account for daily variations in ambient temperature. The authors propose a modification that accurately predicts top oil temperature and can be implemented in an online system. This model is verified using data from a large power transformer in service
  • Keywords
    power transformer insulation; power transformers; thermal analysis; transformer oil; IEEE model; online diagnosis system; online monitoring system; power transformer top oil temperature; thermal modelling; top oil temperature rise; Condition monitoring; Electromagnetic modeling; Heat transfer; Laboratories; Oil insulation; Petroleum; Power measurement; Predictive models; Temperature dependence; Thermal loading;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.568247
  • Filename
    568247