Title :
Optimization of the fault-current limiting transformer
Author :
Brochu, Jacques ; Lemay, Jacques
Author_Institution :
Centre d´´Innovation sur le Transp. d´´Energie du Quebec, Varennes, Que., Canada
fDate :
1/1/2001 12:00:00 AM
Abstract :
The fault current limiting transformer (FCLT) presented by J. Brochu et al. (see IEEE Trans. Power Delivery, vol.13, p.233-40, 1998) was designed with the purpose of increasing the total capacity of a transformer station without increasing short-circuit currents. In situations where such an IPC is closely coupled with parallel transformers, the FCLT installation can be simplified. The purpose of this letter is to describe the enhanced capabilities and outline the basic design criteria for this innovative IPC application. An application example provides typical component ratings, space requirements, and a budget cost estimate
Keywords :
fault current limiters; power transformers; transformer substations; budget cost estimate; component ratings; fault-current limiting transformer; parallel transformers; short-circuit currents; space requirements; transformer station total capacity increase; Capacitors; Circuit faults; Costs; Environmental economics; Fault currents; Impedance; Inductors; Reactive power; Substations; Voltage control;
Journal_Title :
Power Engineering Review, IEEE