DocumentCode :
1424026
Title :
Analysis of voltage collapse mechanisms in state space
Author :
Bao, L. ; Duan, X. ; He, Y.
Author_Institution :
Dept. of Electr. Power Eng., Huazhong Univ. of Sci. & Technol., Hubei, China
Volume :
147
Issue :
6
fYear :
2000
fDate :
11/1/2000 12:00:00 AM
Firstpage :
395
Lastpage :
400
Abstract :
The effects of the generator excitation current limit, the on-load tap changer (OLTC) and load dynamics on voltage stability are analysed in state space. The variation of the number and coordinates of the equilibrium points with parameters of the system are discussed. In addition, a small-disturbance voltage stability region of a simple system is constructed. When the dynamic aspect of voltage collapse is considered, it is more convenient to analyse it in the state space rather than in the input/output parameter space. The voltage stability of a system is determined by the dynamic characteristics of both the OLTC and the load. The generator excitation current limit affects the voltage stability by changing the small-disturbance voltage stability region and the equilibrium points of the system. After a small disturbance, the mode of voltage instability, fast instability or longer-term instability, depends on the composition of the load as well as the value of the system reactance
Keywords :
electric reactance; load (electric); power system dynamic stability; power transformers; state-space methods; fast instability; generator excitation current limit; input/output parameter space; load dynamics; longer-term instability; on-load tap changer; small-disturbance voltage stability region; state space; system reactance; voltage collapse mechanisms analysis; voltage stability;
fLanguage :
English
Journal_Title :
Generation, Transmission and Distribution, IEE Proceedings-
Publisher :
iet
ISSN :
1350-2360
Type :
jour
DOI :
10.1049/ip-gtd:20000670
Filename :
894403