• DocumentCode
    1424098
  • Title

    Surge-transference characteristics of generator-transformer installations

  • Author

    White, E.L.

  • Author_Institution
    Electrical Research Association, Leatherhead, UK
  • Volume
    116
  • Issue
    4
  • fYear
    1969
  • fDate
    4/1/1969 12:00:00 AM
  • Firstpage
    575
  • Lastpage
    587
  • Abstract
    Progressive increases in generator outputs and in transmission voltages necessitate a re-examination of the relevance of surge transference to the security of the insulation of generators. Simple equivalent circuits representing inductive and capacitive transference are taken as a basis for the analysis of oscillograms of transferred voltages recorded in low-voltage impulse tests on three generator installations. Reasons are found for substantial differences between the measured peak voltages and values calculated from consideration of inductive transference alone. The analysis accounts for the observed asymmetric distributions of voltage between the three phases, and supports the use of a simple lumped-parameter circuit to represent the generator impedance in calculations. From the experimental results, the highest overvoltages to which the three generators could be exposed by surge transference are calculated.
  • Keywords
    AC generators; power systems; surge protection; transformers;
  • fLanguage
    English
  • Journal_Title
    Electrical Engineers, Proceedings of the Institution of
  • Publisher
    iet
  • ISSN
    0020-3270
  • Type

    jour

  • DOI
    10.1049/piee.1969.0116
  • Filename
    5249667