DocumentCode :
1424245
Title :
Online Tracking of Thévenin Equivalent Parameters Using PMU Measurements
Author :
Abdelkader, Sobhy M. ; Morrow, D. John
Author_Institution :
Electr. Eng. Dept., Mansoura Univ., Mansoura, Egypt
Volume :
27
Issue :
2
fYear :
2012
fDate :
5/1/2012 12:00:00 AM
Firstpage :
975
Lastpage :
983
Abstract :
This paper presents a new method for tracking Thévenin equivalent parameters for a power system at a node using local phasor measurement unit (PMU) measurements. Three consecutive phasor measurements for voltage and current, recorded at one location, are used. The phase drifts caused by the measurement slip frequency are first determined and phase angles of the measured phasors are corrected so that the corrected phasors are synchronized to the same reference. The synchronized phasors are then used to determine the equivalent Thévenin parameters of the system.
Keywords :
phasor measurement; PMU measurements; Thevenin equivalent parameters; local phasor measurement unit measurements; measurement slip frequency; online tracking; phase drifts; synchronized phasors; Current measurement; Frequency measurement; Phase measurement; Phasor measurement units; Power system stability; Synchronization; Voltage measurement; Phasor measurement; Thévenin equivalent; power system;
fLanguage :
English
Journal_Title :
Power Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8950
Type :
jour
DOI :
10.1109/TPWRS.2011.2178868