• DocumentCode
    1426002
  • Title

    A New Digital Distance Relaying Scheme for Series-Compensated Double-Circuit Line During Open Conductor and Ground Fault

  • Author

    Makwana, Vijay H. ; Bhalja, Bhavesh R.

  • Author_Institution
    Dept. of Electr. Eng., G.H. Patel Coll. of Eng. & Technol., Vallabh Vidyanag, India
  • Volume
    27
  • Issue
    2
  • fYear
    2012
  • fDate
    4/1/2012 12:00:00 AM
  • Firstpage
    910
  • Lastpage
    917
  • Abstract
    This paper presents a new digital distance relaying scheme which takes care of a simultaneous open conductor and ground fault occurring coincidently on the same phase at the same point on a series-compensated double-circuit line. The effect of series compensation, mutual zero-sequence coupling, remote infeed/outfeed, and fault resistance on the relay reach has been considered by the proposed scheme. The conventional digital distance relay having facility of series compensation fails to provide adequate protection in the presence of such conditions. The proposed scheme is based on the derivation of the compensated values of impedance using symmetrical component theory. To validate the proposed scheme, numerous computer simulations have been carried out using MATLAB/SIMULINK software on an existing 400-kV, 300-km-long series-compensated double-circuit transmission line. At the end, a comparative evaluation between the proposed scheme and the conventional scheme having a facility of series compensation is carried out. Simulation results demonstrate the effectiveness of the proposed scheme since the percentage error is within ±4.19%.
  • Keywords
    power system faults; power system relaying; power transmission lines; MATLAB-SIMULINK software; digital distance relaying scheme; fault resistance; ground fault; mutual zero-sequence coupling; open conductor; series compensation; series-compensated double-circuit line; series-compensated double-circuit transmission line; size 300 km; symmetrical component theory; voltage 400 kV; Circuit faults; Conductors; Electrical resistance measurement; Impedance; Impedance measurement; Protective relaying; Resistance; Digital distance protection; mutual coupling; open conductor and ground fault; series-compensated double-circuit line;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2011.2178438
  • Filename
    6134696