DocumentCode :
1426128
Title :
Wide-area current differential backup protection employing broadband communications and time transfer systems
Author :
Serizawa, U. ; Myoujin, M. ; Kitamura, K. ; Sugaya, N. ; Hori, M. ; Takeuchi, A. ; Shuto, I. ; Inukai, Motoharu
Author_Institution :
Central Res. Inst. of Electr. Power Ind., Tokyo, Japan
Volume :
13
Issue :
4
fYear :
1998
fDate :
10/1/1998 12:00:00 AM
Firstpage :
1046
Lastpage :
1052
Abstract :
As power systems grow larger, it is becoming difficult to achieve reach and time coordination in backup protection when using distance relays. To cope with those problems, current differential backup protection for a busbar and transmission circuits connected to that busbar on an inter-station or wide-area basis is proposed. The proposed system can operate better than conventional systems with respect to operation time, section selectivity, etc. A system configuration is also proposed to utilize ATM transmission networks and time synchronous systems which make the construction and operation of the proposed wide-area protection system easy and flexible
Keywords :
asynchronous transfer mode; broadband networks; power system control; power system protection; power system relaying; relay protection; telecontrol; ATM transmission networks; broadband communications; busbar; current differential backup protection; operation time; section selectivity; time coordination; time synchronous systems; time transfer systems; transmission circuits; wide-area power system protection; Asynchronous transfer mode; Broadband communication; Circuits; Global Positioning System; Load flow; Power system protection; Power system relaying; Power transmission lines; Protective relaying; Substation protection;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.714445