Abstract
The paper is born as a contribution to the IEC 36A Working Group 2 “Seismic qualification of bushings” in order to evaluate the coefficients K (amplification factor between the ground and the transformer bushing flange) and R (response factor of the bushing itself) as defined in the IEC 61463. These coefficients allow the definition of the seismic severity at the flange level to be used for static calculations and vibrational tests on high voltage bushings. For the evaluation of these coefficients, both experimental on-site dynamic tests and numerical finite element analyses have been performed for a 160 MVA, 230/135 kV power transformer. The natural frequencies and the seismic response of the whole transformer (tank, oil conservator and HV bushings), subjected to different earthquakes, have been calculated. A comparison between the calculated coefficients (K and R) and those established by the IEC 61463 is illustrated
Keywords
bushings; earthquakes; finite element analysis; insulator testing; power transformer insulation; power transformer testing; seismology; 135 kV; 160 MVA; 230 kV; IEC 36A Working Group 2; amplification factor; experimental onsite dynamic tests; natural frequencies; numerical finite element analyses; response factor; seismic qualification; seismic response; seismic severity; transformer bushing flange; transformer high voltage bushings; Finite element methods; Flanges; IEC standards; Insulators; Oil insulation; Performance analysis; Performance evaluation; Power transformers; Qualifications; Testing;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.714486
Filename
714486
Link To Document